Middle Static Ceiling Concealed Ducted
Middle Static Ceiling Concealed Ducted
FBA-BVMA

Installation is possible even in buildings with narrow ceiling spaces.

Controls the airflow rate using a remote controller during test run.

It is automatically adjusted to approximately ±10% of the rated H tap airflow.

Key Features

Adjustable E.S.P
External static pressure can be controlled to within a range of 50 Pa to 150 Pa by using a DC fan motor. Comfort airflow is achieved in accordance with conditions such as duct length.

Drain pan maintenance check window
This makes it possible to inspect for drain pan dirt and to confirm drainage during installation without the use of tools.

High Efficiency
DC fan motor and DC drain pump
These are utilized to improve energy efficiency.

Clean
Silver ion anti-bacterial drain pan
A built-in antibacterial treatment that uses silver ion in the drain pan prevents the growth of slime, bacterial, and mould that causes odours and clogging.

Other Features

Interlock control
As an energy saving feature, the room air conditioning unit can be interlocked with the hotel key card system. Using a 3rd-party building management system, air conditioning and lighting can be interlocked.

Higher lift is realized
A built-in DC drain pump with standard accessory is utilized.

DIII-NET communication standard
Connection to centralized control system is available without need for an optional adaptor.

Bottom suction is available
Wiring and servicing can be done from the underside of the unit (an option part required)

 

Product Specification
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE (1 Phase)

 

50

60

71

100

125

140

Model Name

Indoor Unit

 

FBA50BVMA

FBA60BVMA

FBA71BVMA

FBA100BVMA

FBA125BVMA

FBA140BVMA

Outdoor Unit

 

RZF50CVM

RZF60CVM

RZF71CVM

RZF100CVM

RZF125CVM

RZF140CVM

Power Supply

Indoor Unit

1 phase, 220-240V, 50Hz

Outdoor Unit

1 phase, 220-240V, 50Hz

Cooling Capacity

Rated (Min. - Max.)

Rated

(Min - Max)

kW

5.0

(3.2-5.6)

6.0

(3.2-6.0)

7.1

(3.2-8.0)

10.0

(5.0-11.2)

12.5

(5.7-14.0)

14.0

(6.2-15.5)

Btu/h

17,100

(10,900-19,100)

20,500

(10,900-20,500)

24,200

(10,900-27,300)

34,100

(17,100-38,200)

42,700

(19,500-47,800)

47,800

(21,200-52,900)

Power consumption

Cooling

kW

1.35

1.64

2.15

3.01

4.44

5.69

COP

W/W

3.70

3.66

3.30

3.32

2.82

2.46

CSPF

Wh/Wh

5.51

5.30

5.19

4.88

4.70

4.47

 

 

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE (3 Phase)

 

71

100

125

140

Model Name

Indoor Unit

 

FBA71BVMA

FBA100BVMA

FBA125BVMA

FBA140BVMA

Outdoor Unit

 

RZF71CYM

RZF100CYM

RZF125CYM

RZF140CYM

Power Supply

Indoor Unit

1 phase, 220-240V, 50Hz

Outdoor Unit

3 phase, 380-415V, 50Hz

Cooling Capacity

Rated (Min. - Max.)

Rated

(Min - Max)

kW

7.1

(3.2-8.0)

10.0

(5.0-11.2)

11.5

(5.7-14.0)

14.0

(6.2-15.5)

Btu/h

24,200

(10,900-27,300)

34,100

(17,100-38,200)

42,700

(19,500-47,800)

47,800

(21,100-52,900)

Power consumption

Cooling

kW

2.15

3.01

4.44

5.69

COP

W/W

3.30

3.32

2.82

2.46

CSPF

Wh/Wh

5.19

4.88

4.70

4.47